LG R410A

×

Download Template

See PM Schedule See Parts List

Product Info

The ARUN/ARNU Series is a 10HP heat pump air conditioner system. It includes an outdoor unit and various indoor unit models such as ceiling cassette, art cool, and ceiling concealed duct types. The system uses R410A refrigerant and features advanced controls and protection functions.

Preventive Maintenance Schedule

Every 8000 hours:

  • Replace compressor oil
  • Clean heat exchanger

Daily:

  • Check for refrigerant leakage
  • Check for slack in power or transmission cables

Every 6 months:

  • Check insulation resistance of compressor
  • Check that high/low pressure valves are fully opened

Parts List

  • Compressor: Pressurizes the refrigerant to high temperature and pressure (Part Number: Not Available)
  • Inverter Fan Motor: Adjusts outdoor fan speed by varying the frequency from 0-65Hz (Part Number: Not Available)
  • Outdoor LEV: Adjusts refrigerant flow based on outdoor unit superheat level (Part Number: Not Available)
  • Subcooler LEV: Adjusts refrigerant flow based on excessive cold heat exchanger outlet temperature (Part Number: Not Available)
  • Oil Pass Valve: Not Available (Part Number: Not Available)
  • Oil Equalization Valve: Not Available (Part Number: Not Available)
  • Hot Gas Bypass Valve: Stabilizes the system by supplying high pressure gas to the low pressure part (Part Number: Not Available)
  • 4 Way Valve: Switches between cooling and heating modes (Part Number: Not Available)
  • Outdoor Check Valve: Allows refrigerant flow in cooling mode (Part Number: Not Available)
  • Discharge Check Valve: Prevents reverse refrigerant flow into the compressor (Part Number: Not Available)
  • High Pressure Switch: Mechanically stops the compressor at high pressure limit (Part Number: Not Available)
  • High Pressure Sensor: Measures high pressure of the system (Part Number: Not Available)
  • Low Pressure Sensor: Measures low pressure of the system (Part Number: Not Available)
  • Heat Exchanger Temperature Sensor: Measures outdoor heat exchanger temperature for control (Part Number: Not Available)
  • Compressor Discharge Temperature Sensor: Measures compressor discharge temperature for protection and control (Part Number: Not Available)
  • Air Temperature Sensor: Measures outdoor air temperature (Part Number: Not Available)
  • Suction Temperature Sensor: Measures refrigerant suction pipe temperature for superheat control (Part Number: Not Available)
  • Liquid Tube Temperature Sensor: Measures refrigerant liquid pipe temperature for subcool control (Part Number: Not Available)
  • Subcooler Outlet Temperature Sensor: Measures subcooler outlet temperature for superheat control (Part Number: Not Available)
  • Subcooler Inlet Temperature Sensor: Measures subcooler inlet temperature for superheat control (Part Number: Not Available)

Product Specs Sheet

  • Cooling Capacity: 28,000W (95,500 Btu/h)
  • Heating Capacity: 31,500W (107,500 Btu/h)
  • Dimensions (W*H*D): 1400*1790*650 mm (55.1*70.5*25.6 inch)
  • Net Weight: 350 kg (771.6 lbs)
  • Refrigerant: R410A
  • Power Supply: 3Ø, 380 ~ 415V, 50Hz

Troubleshooting

  • Compressor not operating:
    • Check compressor insulation resistance
    • Check compressor windings for open or short circuit
  • Outdoor fan not operating:
    • Check fan motor connector connection
    • Check for fan lock, remove any obstructions
    • Replace fan motor if defective
  • LEV not operating properly:
    • Check LEV coil resistance
    • Check for LEV lock or clogging, replace LEV if defective
  • High pressure error:
    • Check indoor/outdoor fan operation
    • Check for refrigerant overcharge, adjust as needed
    • Check LEV, 4-way valve, and other components
  • Low pressure error:
    • Check indoor/outdoor fan operation
    • Check for refrigerant leakage, add refrigerant as needed
    • Check LEV and other components

Please
note that any procedure, checklist, or other document available on Limble is provided for general education and
information only and does not constitute legal, medical, or financial advice. Limble makes the materials available
AS IS and AS PROVIDED, without warranties of any kind. By downloading or using any such materials, you assume the
risk that they may not be appropriate for your specific situation and agree that you are solely responsible for any
such use, including compliance with applicable law and with meeting any conditions of product warranties. It is
recommended to contact OEM for the most accurate information.

f3794e9d-f0da-43a5-ab9d-79e5a37b6211

Configure and custumize to fit your needs

  • Reduce downtime

    Increase Productivity

    Prioritize and complete work orders faster with efficient, collaborative software your team will love using.

  • Compliance and audits

    Reduce Downtime

    Avoid setbacks with a proactive, preventive maintenance strategy and move fast when emergencies do happen.

  • See every work order

    World Class Support

    Limble’s support team is ready to answer any questions you have in 60 seconds or less, 24/7.

Want to see Limble in Action?

FAQs

Why are Standard Operating Procedures (SOP) Important?

SOPs ensure consistency, efficiency, and safety by providing clear guidelines for tasks. They streamline training, maintain quality, ensure compliance, and support continuous improvement and accountability.

What is CMMS?

CMMS stands for Computerized Maintenance Management System. CMMS software helps businesses manage, automate, and streamline all of their maintenance operations.

Is Limble’s CMMS Mobile Friendly?

Limble is consistently rated Easiest-to-Use CMMS on review sites like G2, Capterra, and Software Advice. And our customers agree. With our mobile CMMS app, teams experience 30%+ better productivity, on average, requiring little to no training or ramp-up time. Our CMMS app can travel with your team, no matter where they go! Visit our App Store or Google Play for more information.

Integration

Limble provides seamless, pre-built CMMS Integrations with the most widely used software systems. That means no help from a developer or your IT team is required. Learn more about our integrations.

Security

At Limble, our world-class data security practices ensure your account information is safe. We use state-of-the-art technologies and industry best practices to maintain a secure infrastructure, including SOC-II Type II certification, regular penetration testing, and continuous security training for our staff.

X

Request a Demo

Share your contact details below and someone from our team will reach out as soon as possible.